| Small office or edge rack | 120 V, 15 A, single-phase | 1.80 kVA maximum circuit rating Approximately 1.44 kW at 0.80 power factor | Up to 1.15 kW at an 80% planning limit | 8–12 × 5-15R receptacles | Network switches, routers, firewalls, compact servers, and small UPS systems | Basic metering, overload protection, 1U horizontal or vertical mounting |
| Standard single-phase server rack | 208 V, 20 A, single-phase | 4.16 kVA maximum circuit rating Approximately 3.33 kW at 0.80 power factor | Up to 3.33 kW at an 80% planning limit | 12–24 × C13; optional C19 outlets | General-purpose servers, storage arrays, network appliances, and telecom equipment | Network monitoring, remote current readings, temperature sensing, and branch-level alerts |
| International 230 V rack | 230 V, 16 A, single-phase | 3.68 kVA maximum circuit rating Approximately 2.94 kW at 0.80 power factor | Up to 2.94 kW at an 80% planning limit | 12–24 × C13; 2–6 × C19 where required | Rack servers and IT equipment using IEC power connections | Metered input, outlet-level switching, sequencing, and remote reboot control |
| High-density single-phase rack | 230 V, 32 A, single-phase | 7.36 kVA maximum circuit rating Approximately 5.89 kW at 0.80 power factor | Up to 5.89 kW at an 80% planning limit | 18–36 × C13; 4–12 × C19 | Virtualization hosts, dense storage, GPU workstations, and high-wattage servers | Load balancing, outlet groups, circuit alarms, environmental sensors, and IP management |
| North American high-density rack | 208 V, 30 A, single-phase | 6.24 kVA maximum circuit rating Approximately 4.99 kW at 0.80 power factor | Up to 4.99 kW at an 80% planning limit | 24–36 × C13; 4–12 × C19 | High-density compute, storage, and mixed enterprise IT loads | Per-outlet metering, remote switching, user access control, and alarm notifications |
| Three-phase data-center rack | 400 V, 16 A, three-phase | 11.09 kVA maximum circuit rating Approximately 8.87 kW at 0.80 power factor | Up to 8.87 kW at an 80% planning limit | 18–36 × C13; 6–12 × C19 | High-density server racks and installations requiring better phase utilization | Per-phase monitoring, phase imbalance alerts, power-quality readings, and remote control |
| Very high-density three-phase rack | 415 V, 32 A, three-phase | 23.01 kVA maximum circuit rating Approximately 18.41 kW at 0.80 power factor | Up to 18.41 kW at an 80% planning limit | 24–42 × C13; 8–18 × C19 | Accelerated-computing systems, dense virtualization, and high-performance workloads | Three-phase load balancing, detailed energy reporting, outlet-level control, and environmental integration |
| Telecom or shallow network cabinet | 230 V, 10 A, single-phase | 2.30 kVA maximum circuit rating Approximately 1.84 kW at 0.80 power factor | Up to 1.84 kW at an 80% planning limit | 8–12 × C13 or regional IEC-compatible outlets | Switches, wireless controllers, transmission equipment, and compact edge appliances | Compact vertical mounting, basic current display, surge protection, and remote alarm contacts |